The Signaline ESWD-2 is a 2 zone water detection control panel. Designed for use with the Signaline range of water leak detection cables it is ideal for use for protecting critical applications where equipment may be vulnerable to water ingress.
PLEASE NOTE: These panels are made to order - lead time is 3-4 weeks
Signaline ESWD-2 Water Detection Control Panel Specification
End of Line Device : 4k7 Ohm 5% 0.25w resistor
IP Rating : IP30
Operating Temperature : -5°c to +40°c
Operating Humidity : <95%
Standby Current : 75mA (2 zone) 85mA (4 zone)
Alarm Circuits : 2 fully monitored, each fused @500mA
Alarm Load : 800ma shared between all sounder outputs.
Common Alarm Relay : Volt free no/c/nc contact rated 3 amp @30 Vdc
Common Fault Relay : Volt free no/c/nc contact rated 3 amp @30 Vdc
External Inputs : Class change and Alert pulse sounders / Non latching switched –ve inputs / Max input voltage 28Vdc
Outputs : Water alarm and fault common outputs / Switched –ve voltage outputs for external relay control / max load 40mA