- Manufacturer : Kidde
- Part Code : ADELCU-EOL
- Alarmline II Digital End Of Line Unit
- EN54-28:2016 Certified
Kidde ADELCU-EOL Alarmline II EOL Unit
The Kidde ADELCU-EOL is a replacement end-of-line unit for use with the AlarmLine II Digital EN Linear Heat Detection Controller and AlarmLine II Digital EN Linear Heat Detection Cable.
Functional testing
Internally the unit features 4 switches, which can be used to simulate a fire or fault on each of the zones. There are two push-buttons, one for each zone, which simulate a fire by connecting the two cable cores when the button is pressed. Similarly there are two switches, which under normal conditions connect the end-of-line resistor across the cable, for each zone. However when the switch is changed, this create an open circuit which in turn raises a fault on the controller. Via these switches it is easy to functionally test the system.
Kidde ADELCU-EOL Alarmline II EOL Features
- Quickly simulate a fault condition
- Quickly simulate an alarm condition
- Supplied with 2 IP67 rated cable glands
- Secure, weatherproof enclosure
- RoHS Compliant, CE & EN54-28:2016 Certified