Available in Red or White - Red Requires An Extra 14 Day Lead Time From Ordering
2, 4 and 8 zone non-expandable control panels
Up to 32 conventional smoke and/or heat detectors per zone
Active End of Line monitoring
Programmable non-latching zones
Delay timer programmable on/off per zone
Zone coincidence programmable for adjacent zones
Three Access Levels
One man test
Supervised auxiliary 24 volt output
2 supervised/ monitored sounder circuits
3 remote inputs used for activation of Class Change, Day/Night mode, and Reset
2 Relay outputs fire and fault
Power supply 1,7A at 28V DC
Fully EN54 part 2 and 4 compliant
Repeater output
Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
Multiplexed output for sounders per zone (GFE-MPX-SNDR)
Addressable Loop Interface card (GFE-ADLI)
GFE 2-8 Zone Conventional Fire Alarm Panel
The ORION range of conventional control panels features three models with 2, 4 and 8 Zones of detection. Housed in a stylish modern ABS housing, the ORION is the ideal control panel for smaller installations.
Designed and manufactured to comply with the requirements of EN54 parts 2 and 4(1998) the ORION uses active End of Line monitoring to permit head removal protection as required by BS5839. (detector bases must be fitted with Diode)
Programmable Zone coincidence and alarm delay timer (0-10 min) are standard features to help reduce false alarms.
The one man test facility enables simple and rapid testing of the system at commissioning and during maintenance operations.