  • Manufacturer : Gent by Honeywell
  • Part Number : 13270-02
  • Conventional Fire Alarm Control Panel
  • 2 Detection Zones
  • 2 Conventional Sounder Circuits
  • BS5839 & EN54 Compliant

Gent Xenex Fire Alarm Panel - 2 Zone Conventional 13270-02 LB

FEATURES:-
  • Number of Zones - 2
  • Maximum Load Per Zone - 3mA
  • Number of Sounder Circuits - 2
  • Maximum Sounder Circuit Load - 0.5A per circuit (Total Load Not To Exceed 1A)
  • Batteries (Not Included) - 2 x 12V 2.1Ah (See Related Products)
  • Battery Standby (Using Above Specified Batteries) - 72 Hours plus 0.5 Hours Alarm Load
  • Aux Relay Contacts - 1 N/O and 1 N/C Pair, 1A at 24V
  • Approx Weight (With Batteries) - 5.8Kg
  • Relevant Standard - EN54 Parts 2 and 4
  • Approvals - LPCB Approved to EN54 Parts 2 and 4
  • Cable Entry - 13 Top and 13 Rear
  • Cable Type - BS 6387, 2 Core, min 1.5mm Square CSA
  • Class Change Facility - Via Normally Open Push Button Switch Located No More Than 100m From Panel
  • Temperature - Indoor 0 - 40 Degrees Celcius
This is the Gent Xenex 13270-02LB.  This fire alarm panel complies fully with the European standard EN54 Parts 2 & 4 and can be used on installations meeting BS 5839: Part 1.  Each panel contains its own integral power supply and battery support for up to two alarm sounder circuits, two auxiliary relay contacts, a zone disablement facility and a one man test and commission facility, all simplifying system design, installation and commissioning.
Write Your Own Review
You're reviewing:Gent 13270-02LB Xenex Fire Alarm Panel - 2 Zone Conventional
Your Rating

Our Brands

  • Apollo Logo
  • Ctec Logo
  • Electro Detectors Logo
  • Notifier Logo
  • STI Logo
  • Yuasa Logo
  • Apollo Logo
  • Ctec Logo
  • Electro Detectors Logo
  • Notifier Logo
  • STI Logo
  • Yuasa Logo