Complies with FM 3260 EN54 certified Certified SIL 2
Det-Tronics X3301 Multispectrum Flame Detector
The Det-Tronics X3301 is a multispectrum infrared (MIR) flame detector. It provides unsurpassed detection of fires from light to heavy hydrocarbon fuels combined with the highest degree of false alarm rejection. The detector has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor applications.
The X3301 contains three IR sensors with their associated signal processing circuitry. The standard output configuration includes fire alarm, fault and auxiliary relays, with an isolated 0–20 mA output model with optional HART communication.
The detector provides superior performance in applications that are at the extremes, and where background infrared radiation is a normal condition:
Hangars
Offshore production platforms
Offshore production ships
Refineries
Production facilities
Loading racks
Compressor stations
Turbine enclosures
Airport water curtains
Automotive Painting
LNG/LPG
Gas Separation Plants
Warehousing
Marine
Features
X3301 TECHNOLOGY FEATURES
Complies with FM 3260
EN54 certified
Certified SIL 2 capable
ATEX Directive compliant
Certified performance to multiple fuel types and fire sizes
EQP models available
Long detection range to carbonaceous fires
HART models available
FDT/DTM capable
Multiple sensitivity levels
Maximum false alarm rejection
Calibrated automatic optical integrity
Reliable flame detection with modulated IR background
Microprocessor controlled heated optics
Third-party approved options for detector verification include Magnetic Optical Integrity and Manual Optical Integrity tests
Tri-color LED indicates detector status and field-of-view (FOV)
RFI and EMC Directive compliant
Event logging with time and date stamp
Integral wiring compartment for ease of installation
Operates under adverse weather conditions and in dirty environments
Benefits
Single detector for multiple hydrocarbon fuels
Low cost of coverage
Ability to detect smaller fires earlier
Detection range of up to 125 feet for methane
Better detection zoning capability
Best combination of flame detection and false alarm rejection
Low maintenance costs
Reliable fault diagnostics
Suitable for heavy industrial applications
Explosion/flame proof (Ex d) or increased safety installations (Ex d e) in hazardous locations